TrueAlarm heat detectors are self-restoring and provide rate compensated, fixed temperature sensing, selectable with or without rate-of-rise temperature sensing. Due to its small thermal mass, the detector accurately and quickly measures the local temperature for analysis at the CIE Rate-of-rise temperature detection is selectable for either 8.3°C or 11.1°C per minute. Fixed temperature sensing is independent of rate-of-rise sensing and programmable to operate at 57.2°C or 68°C. In a slow developing fire, the temperature may not increase rapidly enough to operate the rate-of-rise feature, however an alarm will be initiated when the temperature reaches its rated fixed temp setting.
Technical Details
- Width (mm):
- 100.0
- Height (mm):
- 60.0
- Alarm Current (max):
- 10mA
- Ambient Temperature:
- 0 to +50°C
- Dimensions:
- L100 x W100 x H60mm
- External Output Drive (max):
- 5mA
- Length (mm):
- 100
- Operating Voltage:
- 24 to 40Vdc*
- Pack Quantity:
- 1.0
- Quiescent Current (max):
- 400A
- Relative Humidity:
- 10% to 95% (n/cond)
- Single Units:
- Yes
- Weight:
- 100g