Close

Commercial Extended Coverage

VK532 - EC/QREC Upright Sprinkler (K11.2)View larger

VK532 - EC/QREC Upright Sprinkler (K11.2)

Viking EC/QREC Upright Sprinkler VK532 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying design requirements. The extra-large orifice produces the flows required to meet Light and Ordinary Hazard density requirements at lower pressures than standard orifice or large orifice sprinklers. The glass bulb operating element and special deflector characteristics meet the challenges of quick response extended coverage standards. The Model VK532 is cULus Listed as standard and quick response and FM Approved as quick response. The available ENT coating has been investigated for installation in corrosive atmospheres. See technical datasheet for required design and installation criteria.

Viking EC/QREC Upright Sprinkler VK532 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying design requirements. The extra-large orifice produces the flows required to meet Light and Ordinary Hazard density requirements at lower pressures than standard orifice or large orifice sprinklers. The glass bulb operating element and special deflector characteristics meet the challenges of quick response extended coverage standards. The Model VK532 is cULus Listed as standard and quick response and FM Approved as quick response. The available ENT coating has been investigated for installation in corrosive atmospheres. See technical datasheet for required design and installation criteria.



Downloads

TECHNICAL DATA SHEETS
CERTIFICATE
DRAWING
GUIDE
REVIT FILES

Technical Details

  • Maximum Spacing : 6.1 x 6.1m
  • Maximum Working Pressure : 175 psi (12 bar)
  • Minimum Spacing : Per Standards / Listings
  • Model Number : VK532
  • Occupancy Type : Light Hazard, Ordinary Hazard
  • Response Type : Standard/Quick
  • Thread Size : 3/4" NPT (20 mm BSP)

Product Information

Viking EC/QREC Upright Sprinkler VK532 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings to meet varying design requirements. The extra-large orifice produces the flows required to meet Light and Ordinary Hazard density requirements at lower pressures than standard orifice or large orifice sprinklers. The glass bulb operating element and special deflector characteristics meet the challenges of quick response extended coverage standards. The Model VK532 is cULus Listed as standard and quick response and FM Approved as quick response. The available ENT coating has been investigated for installation in corrosive atmospheres. See technical datasheet for required design and installation criteria.

table class="viking-sprinkler-product-desc">Coverage Area (ft / m)Flow (gpm / lpm)Pressure (psi / bar)LIGHT HAZARD16 x 161 (4.9 x 4.9)30 (113.6)7.2 (0.50)18 x 181 (5.5 x 5.5)33 (124.9)8.7 (0.60)20 x 201 (6.1 x 6.1)40 (151.4)12.8 (0.88)ORDINARY HAZARD312 x 121 (3.7 x 3.7)30 (113.6)7.2 (0.50)14 x 141 (4.3 x 4.3)30 (113.6)7.2 (0.50)16 x 162 (4.9 x 4.9)38 (143.9)11.5 (0.79)18 x 182 (5.5 x 5.5)49 (185.5)19.1 (1.32)20 x 202 (6.1 x 6.1)60 (227.1)28.7 (1.98) 1 Available only for quick response.
2 Available only for standard response.
3 Design data listed above is for OH Group 1. See technical datasheet for OH Group 2 data.
See technical datasheet for FM approval criteria