RESOURCES
Universal Flame Simulator Test Kit - FlameStop TV Episode 48
Voting Closes Thursday - Support Ben Parkhill for the FPA Australia Board
Reduce Expensive Fire Brigade Call-Out Fees with the MX850 Series Smoke Detectors
4 Hour Online Training Course on the Vigilant QE20 Emergency Warning Systems - Distributed by FlameS
See allBFP300
Availability date:
Our range of FirePillow - 240 covers a wide variety of applications. Fire Pillow s are the most common - treated fabric bags containing fire retardant granulated rockwool, securing penetrations in fire rated construction against the passage of smoke and the spread of fire. They are best suited to environments where pipes, telecommunications cables, cable trays and service shafts penetrate a fire - rated wall or floor.
We also supply High Performance FirePillows and Intumescent FirePillows for environments where water, oil, chemicals and greater protection are required.
FirePillow - 240 are designed to fire rate wall and floor miscellaneous penetrations which may incorporate cables, ducts, metal pipes, bus bars or the like, where up to 3 hours integrity and up to 3 hours insulation are required.
FirePillow - 240 are fully compliant with AS1530.4 - 1997 and AS407 2.1 - 1992.
The pillows can be used to seal an opening in a floor or wall to a maximum width or height of 400mm by any practical length. The sealing of the pillows is achieved by ‘pillow pressure’ and the use of fire resistant mastic to fill in void s around various pipes, cables and penetrations. The pillows should be stacked tightly in the direction of the least span (up to 400mm) and restrained on the sides by wall section or pillows.
Working from one side of the opening additional pillows should be stacked in the same direction and packed in tightly against the sides of the pillows already installed.
The appropriate sized pillow should be packed around various pipes, cables and penetrating elements, then fire rated sealant used to a depth of 25mm to seal any gaps or voids around the pillows or penetrating elements .
The method of stacking the pillows can vary depending on the shape and dimensions of the various elements that are penetrating the wall or floors.
Testing has been carried out at Warrington Fire Research for 3 hours and achieved the following certification: