Close

Residential Sprinklers

VK480 - Residential Flat Plate Concealed HSW Sprinkler (K4.0)View larger

VK480 - Residential Flat Plate Concealed HSW Sprinkler (K4.0)

Viking's Freedom° Model VK480 5.8 K-factor residential, flat plate concealed, horizontal sidewall sprinkler delivers the installation advantages of a horizontal sidewall sprinkler fully concealed behind a flat cover plate in a residential application. The VK480 is cULus listed for up to 4.9 x 5.5m coverage areas with water flow and pressure requirements that are competitive with a standard recessed sidewall sprinkler. The optional Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is listed/approved as corrosion resistant.

Viking's Freedom° Model VK480 5.8 K-factor residential, flat plate concealed, horizontal sidewall sprinkler delivers the installation advantages of a horizontal sidewall sprinkler fully concealed behind a flat cover plate in a residential application. The VK480 is cULus listed for up to 4.9 x 5.5m coverage areas with water flow and pressure requirements that are competitive with a standard recessed sidewall sprinkler. The optional Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is listed/approved as corrosion resistant.

Technical Details

  • Maximum Spacing : 4.9 x 5.5m
  • Maximum Working Pressure : 175 psi (12 bar)
  • Minimum Spacing : 2.4m
  • Model Number : VK480
  • Occupancy Type : Residential
  • Response Type : Fast (Residential)
  • Thread Size : 1/2" NPT (15 mm BSP)

Product Information

Viking's Freedom° Model VK480 5.8 K-factor residential, flat plate concealed, horizontal sidewall sprinkler delivers the installation advantages of a horizontal sidewall sprinkler fully concealed behind a flat cover plate in a residential application. The VK480 is cULus listed for up to 4.9 x 5.5m coverage areas with water flow and pressure requirements that are competitive with a standard recessed sidewall sprinkler. The optional Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is listed/approved as corrosion resistant.

Coverage Area (ft / m)4-6" (102mm-152mm) From Ceiling6-12" (152mm-305mm) From Ceiling
Flow (gpm / lpm)Pressure (psi / kPa)Flow (gpm / lpm)Pressure (psi / kPa)
12 x 12 (3.7 x 3.7)11 (42)*7.6 (52)12 (46)**9.0 (62)
14 x 14 (4.3 x 4.3)13 (49)*10.6 (73)14 (53)**12.3 (84)
16 x 16 (4.9 x 4.9)16 (61)*16.0 (110)16 (61)**16.0 (110)
16 x 18 (4.9 x 5.5)17 (64)*18.1 (125)18 (68)**20.3 (140)
*Centerline of the sprinkler located 4-3/8" (111mm) to 6-3/8" (162mm) below the ceiling.
**Centerline of the sprinkler located 6-3/8" (162mm) to 12-3/8" (314mm) below the ceiling.
***Flows and pressures shown above refer to the 165° temperature rating. Please consult the product technical datasheet for flows and pressures of the 205° temperature rating.

21 other products in the same category