The Viking Standard Response ELO Upright Sprinkler VK530 is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings to meet design requirements. The extra-large orifice provides greater flows at lower pressures than standard orifice or large orifice sprinklers. This feature allows reduced pipe sizing for hydraulically calculated sprinkler systems, which require high densities of water. Viking Standard Response Extra-Large Orifice Sprinklers may eliminate the need for a fire pump or reduce the size of the pump if it is required. On existing systems, replacing large orifice sprinklers with extra-large orifice sprinklers may provide the higher densities required to allow an increase in the hazard classification of an occupancy.

The Viking Standard Response ELO Upright Sprinkler VK530 is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings to meet design requirements. The extra-large orifice provides greater flows at lower pressures than standard orifice or large orifice sprinklers. This feature allows reduced pipe sizing for hydraulically calculated sprinkler systems, which require high densities of water. Viking Standard Response Extra-Large Orifice Sprinklers may eliminate the need for a fire pump or reduce the size of the pump if it is required. On existing systems, replacing large orifice sprinklers with extra-large orifice sprinklers may provide the higher densities required to allow an increase in the hazard classification of an occupancy.

Technical Details

  • Maximum Spacing : Per Standards / Listings
  • Maximum Working Pressure : 175 psi (12 bar)
  • Minimum Spacing : Per Standards / Listings
  • Model Number : VK530
  • Occupancy Type : Light Hazard, Ordinary Hazard, Extra Hazard, Storage
  • Response Type : Standard
  • Thread Size : 3/4" NPT (20 mm BSP)

Product Information

The Viking Standard Response ELO Upright Sprinkler VK530 is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings to meet design requirements. The extra-large orifice provides greater flows at lower pressures than standard orifice or large orifice sprinklers. This feature allows reduced pipe sizing for hydraulically calculated sprinkler systems, which require high densities of water. Viking Standard Response Extra-Large Orifice Sprinklers may eliminate the need for a fire pump or reduce the size of the pump if it is required. On existing systems, replacing large orifice sprinklers with extra-large orifice sprinklers may provide the higher densities required to allow an increase in the hazard classification of an occupancy.

ExampleDensityStd CMDA Spk Spacing(Q) Flow Rate / Sprinkler(P) Starting PressureExample Water Demand (2,000 ft2 design area)
0.3 gpm/ft2100 ft230 gpm7.2 psi600 gpm
0.4 gpm/ft2100 ft240 gpm12.8 psi800 gpm
0.5 gpm/ft2100 ft250 gpm19.9 psi1,000 gpm
0.6 gpm/ft2100 ft260 gpm28.7 psi1,200 gpm
0.7 gpm/ft2100 ft270 gpm39.1 psi1,400 gpm
0.8 gpm/ft2100 ft280 gpm51.0 psi1,600 gpm