VK595 - Extended Coverage Upright Sprinkler (CMDA/CMSA) (K25.2)View larger

VK595 - Extended Coverage Upright Sprinkler (CMDA/CMSA) (K25.2)

Viking's Model VK595 Extended Coverage Upright Sprinkler is a thermosensitive solder link spray sprinkler with a nominal K-factor of 36.3 for maximum coverage areas of 4.3 x 4.3 m (18.2 sqaure meters).

The VK595 is cULus Listed as a density/area storage sprinkler with a maximum coverage area of 4.3 x 4.3 m, and is also FM Approved as a quick response, extended coverage sprinkler for both storage and non-storage applications. The sprinkler is well-suited for extra hazard, high-pile storage, rack storage, and “big box” retail applications. As an extended coverage sprinkler, the VK595 can reduce installation costs by decreasing the overall number of sprinklers required in a system. Additionally, the larger K-factor can provide the flows needed for higher-density requirements at significantly lower operating pressures. The VK595 also allows for greater installation flexibility relative to obstructions, when compared to ESFR storage sprinklers. The sprinkler is cULus Listed for use within trusses or bar joist having non-combustible web members greater than 25 mm, provided that standard “four times” obstruction rules are followed.

The VK595 is available in 74°C and 101°C temperature ratings.

Viking's Model VK595 Extended Coverage Upright Sprinkler is a thermosensitive solder link spray sprinkler with a nominal K-factor of 36.3 for maximum coverage areas of 4.3 x 4.3 m (18.2 sqaure meters).

The VK595 is cULus Listed as a density/area storage sprinkler with a maximum coverage area of 4.3 x 4.3 m, and is also FM Approved as a quick response, extended coverage sprinkler for both storage and non-storage applications. The sprinkler is well-suited for extra hazard, high-pile storage, rack storage, and “big box” retail applications. As an extended coverage sprinkler, the VK595 can reduce installation costs by decreasing the overall number of sprinklers required in a system. Additionally, the larger K-factor can provide the flows needed for higher-density requirements at significantly lower operating pressures. The VK595 also allows for greater installation flexibility relative to obstructions, when compared to ESFR storage sprinklers. The sprinkler is cULus Listed for use within trusses or bar joist having non-combustible web members greater than 25 mm, provided that standard “four times” obstruction rules are followed.

The VK595 is available in 74°C and 101°C temperature ratings.

Technical Details

  • Maximum Spacing : Per Standards / Listings
  • Maximum Working Pressure : 175 psi (12 bar)
  • Minimum Spacing : Per Standards / Listings
  • Model Number : VK595
  • Occupancy Type : Extra Hazard, Storage
  • Response Type : Standard/Quick
  • Thread Size : 1" NPT (25 mm BSP)

Product Information

Viking's Model VK595 Extended Coverage Upright Sprinkler is a thermosensitive solder link spray sprinkler with a nominal K-factor of 36.3 for maximum coverage areas of 4.3 x 4.3 m (18.2 sqaure meters).

The VK595 is cULus Listed as a density/area storage sprinkler with a maximum coverage area of 4.3 x 4.3 m, and is also FM Approved as a quick response, extended coverage sprinkler for both storage and non-storage applications. The sprinkler is well-suited for extra hazard, high-pile storage, rack storage, and “big box” retail applications. As an extended coverage sprinkler, the VK595 can reduce installation costs by decreasing the overall number of sprinklers required in a system. Additionally, the larger K-factor can provide the flows needed for higher-density requirements at significantly lower operating pressures. The VK595 also allows for greater installation flexibility relative to obstructions, when compared to ESFR storage sprinklers. The sprinkler is cULus Listed for use within trusses or bar joist having non-combustible web members greater than 25 mm, provided that standard “four times” obstruction rules are followed.

The VK595 is available in 74°C and 101°C temperature ratings.

ExampleDensityStd CMDA Spk Spacing(Q) Flow Rate / Sprinkler(P) Starting PressureExample Water Demand (2,000 ft2 design area)
0.3 gpm/ft2196 ft266.7 gpm7.0 psi734 gpm
0.4 gpm/ft2196 ft278.4 gpm9.7 psi863 gpm
0.5 gpm/ft2196 ft298.0 gpm15.1 psi1,078 gpm
0.6 gpm/ft2196 ft2117.6 gpm21.8 psi1,294 gpm
0.7 gpm/ft2100 ft270.0 gpm7.7 psi1,400 gpm
0.7 gpm/ft2196 ft2137.2 gpm29.6 psi1,509 gpm
0.8 gpm/ft2100 ft280.0 gpm10.1 psi1,600 gpm
0.8 gpm/ft2196 ft2156.8 gpm38.7 psi1,725 gpm