Availability date:
Maximum working height: 6.3m
Average test time: 120 seconds (1%/ft/minute fast ramp, 0.5%/ft/minute slow ramp)
Average calibration time:* 40 seconds
Average clearing time:* 120 seconds
Average tests per aerosol/canister 100 tests
Maximum obscuration for ionization: 4.00 %/ft
Maximum obscuration for photoelectric: 6.00 %/ft
Resolution: 0.01 %/ft
Average battery life: 8-10 hours testing on a full charge *can be conducted whilst walking between detectors
Environmentally friendly, non-flammable, non toxic.
A Safety Data Sheet is available on request.
In operation: Self-calibrates before each test
Servicing intervals: 1 year recommended, but max interval 5000 tests
Operating temperature: +10°C to +35°C
Storage temperature: -10°C to +50°C
(Do not store in direct sunlight)
Humidity: 0-85% RH non-condensing
Weight of main unit (incl. aerosol canister): 3kg