RESOURCES
New Quick-Connect Metal Grille Flush Mount Speaker - FlameStop TV Episode 49
Universal Flame Simulator Test Kit - FlameStop TV Episode 48
Voting Closes Thursday - Support Ben Parkhill for the FPA Australia Board
Reduce Expensive Fire Brigade Call-Out Fees with the MX850 Series Smoke Detectors
See allP-VEP-A00-1P
The VESDA-E VEP series of smoke detectors bring the latest and most advanced detection technology to provide very early warning and the best nuisance alarm rejection to a wide range of applications. Built on the Flair detection technology and years of application experience, VEP detectors achieve consistent performance over their lifetime via absolute calibration. In addition, the VEP delivers a range of revolutionary features that provide user value.
Availability date:
The VESDA-E VEP series of smoke detectors bring the latest and most advanced detection technology to provide very early warning and the best nuisance alarm rejection to a wide range of applications. Built on the Flair detection technology and years of application experience, VEP detectors achieve consistent performance over their lifetime via absolute calibration. In addition, the VEP delivers a range of revolutionary features that provide user value.
The VESDA-E VEP series of smoke detectors bring the latest and most advanced detection technology to provide very early warning and the best nuisance alarm rejection to a wide range of applications. Built on the Flair detection technology and years of application experience, VEP detectors achieve consistent performance over their lifetime via absolute calibration. In addition, the VEP delivers a range of revolutionary features that provide user value.
• Accommodation | • Hospitals & Healthcare | • Power Generation |
• Correctional Facilities | • Insurance | • Records Storage |
• Clean Rooms | • Marine | • Retail |
• Cold Storage | • Nuclear Facilities | • Transportation |
• Cultural / Heritage | • Offices | • Wind Power Generation |
• Data & Telecom | • Oil & Gas | • Warehousing |
• Education | • Portable Switch Rooms | And Many More... |
The VESDA-E VEP series of aspirating smoke detectors extend the reach of the VESDA-E platform to a wide range of applications. VEP sensitivity range is from 0.005-20%/m (0.0016-6.25%/ft) and provides up to 40 Class A holes. VEP is equipped with a powerful aspirator that provides a total of 130 m (427 ft) in the one pipe model and 560 m (1,837 ft) in the four pipe model. VEP also provides StaX and Analytics support together with Ethernet, WiFi, USB and VESDAnet capabilities.
Flair is the revolutionary new detection chamber that forms the core of VESDA-E VEP, providing better detection, fewer nuisance alarms, higher stability, increased longevity and particle characterisation. Direct imaging of the sampled particles using a CMOS imager combined with multiple photo-diodes allow vastly more data that can be used to derive actionable information about the observed particles using analytics.
One Pipe VEP | Four Pipe VEP | ||||
Supply Voltage | 18-30VDC (24V Nominal) | ||||
Power Consumption @ 24 VDC | P-VEP-A00-1P | P-VEP-A00-P | P-VEP-A10-P | ||
Aspirator Setting | Fixed | 1 | 5 | 1 | 5 |
Power (Quiescent) | 8.8W | 7.0W | 8.8W | 8.2W | 10.0W |
Power (In Alarm) | 9.6W | 7.8W | 9.6W | 10.4W | 11.6W |
Dimensions (WHD): | 350mm x 225mm x 135mm | ||||
Weight | 4.0kg | 4.0kg | 4.1kg | ||
Operating Conditions | Ambient: 0°C to 39°C | ||||
Sampled Air: -20°C to 60°C | |||||
Tested to: -20°C to 55°C | |||||
UL: -20°C to 50°C | |||||
Humidity: 10% to 95% RH, non-condensing | |||||
Area Coverage | 1,000m2 | 2,000m2 | |||
Min. Airflow Per Pipe | 15 l/m | ||||
Pipe Length (Linear) | 100m | 280m | |||
Pipe Lengths Depending On Number of Pipes in Use | 1 Pipe | 1 Pipe | 2 Pipe | 3 Pipe | 4 Pipe |
100 m | 110 m | 100 m | 80 m | 70 m | |
Analytics | DieselTrace™, DustTrace™, WireTrace™ | ||||
No. of Holes (A/B/C) | 30/40/45 | 40/80/100 | |||
Computer design tool | ASPIRE | ||||
Relays | 7 programmable relays (latching or non-latching states) | ||||
Contacts rated 2 A @ 30 VDC (Resistive) | |||||
Dynamic Range | 0.001% to 32% obs/m | ||||
Sensitivity Range | 0.005 to 20% obs/m | ||||
Software features | Event log: Up to 20,000 events |