The BOSS Thermal Defence System has been developed to prevent the passage of fire and smoke between fire rated compartments where service penetrations exist, such as cables, cable trays and pipe work. The BOSS Thermal Defence S ystem consists of 2 elements:
The TDW is designed to allow movement within the services, maintain necessary insulation on services and prevent temperature rise of services throughout a fire. At normal temperatures, the TDW remains flexible to permit thermal and mechanical movement of the pipes and cables.
Thermal Defence Wrap is a sheathed woven intumescent technology of bio - soluble vitreous material, graphite and flexible organic binders. It will activate in a fire to expand and maintain compartmentalisation for 2 hours.
The advantages of the Thermal Defence Wrap are as follows:
BOSS Thermal Defence System is designed for maintaining compartmentalisation where services, such as cables and pipes, penetrate fire rated walls and floors. BOSS proven passive products provide excellent protection, both in maintaining the integrity of the fire rated seal and also in insulating the service. Use BOSS Thermal Defence to insulate:
in any environment requirement up to - /120/120 on both aperture seals and penetrating services. BOSS Thermal Defence System are fully approved to AS1530.4(2005) and AS4072(2005).
The BOSS Thermal Defence System has the following Test & Assessment references:
Exova Warrington Report 26325 - 02
28th September 2011
Tested to - /120/120 to AS 1530.4(2005) and AS4072.1(2005)
Exova Warrington Report 304406/A
26th May 2011
Tested to - /120/120 to EN1366.3
The BOSS Thermal Defence System is straight forward to install.
S - Line Pillows fill the aperture up to 1.1m x 1.1m in masonry walls around the penetrating services. Once the pillows are installed, the Thermal Defence System is wrapped around the services (depending on cable/pipe configuration), and trimmed to suit the circumference.
The TDW does not need to overlap itself on the penetrations, they can simply butt together and held in place with Al - Foil duct tape or binding wire.
The TDW is then simply pushed up firmly against the surface of the aperture to provide a close fit and any gaps can be sealed with FireMastic - 300.
If a more solid and permanent structure is required, BOSS FireMortar - 360 can be use d to fill the wall aperture. In this case, the aperture needs to be prepared with formwork as per normal mortar installations then BOSS Bulkhead Batts are added to the immediate surround of the penetrating service. The TDWs are then fitted in the same way as the S - Line pillow system above.